OIP WALL BUSHINGS /OIL TO OIL BUSHINGS


Rated Voltage : 24 kV ~ 245 kV

Rated Current : 400 A ~ 3150 A*

Standard : IEC-60137:2017 OR IEEE C.57.19.00/01

Connection : Draw lead/Draw Rod/Solid Conductor

Housing : Porcelain/Composite Silicone-Polymer

*Customized Rated Current >3150A are available upon request

We offer an extensive range of OIP (Oil impregnated Paper) bushings also for the wall through applications as well as Oil-Oil applications inside transformer cable box. Considerable customization is available based on the customer s needs for these products, and we continue to supply these specialized solutions to many customers in India and globally.

  • Rated Voltage 24 kV- 245 kV for IEC range OR 25 kV - 161 kV for IEEE range
  • Rated Current 400 A 3150 A*
  • Insulation: Oil-impregnated paper Hermetically sealed
  • Application: Transformer Cable box/ Wall through (Outdoor-Indoor, Indoor-Outdoor)
  • Type: Oil to Oil/ Air to Air
  • Insulator: Porcelain/ Hollow Composite - Silicone
  • Standard: IEC 60137: 2017/ IEEE C57.19.00/01
  • Connection: Draw lead/Draw Rod/Solid Conductor

*Customized Rated Current >3150A are available upon request

**Detailed drawings of our bushing variants are available upon request.

  • Manufacturing and field experience of more than 12,000 Bushings
  • Computer-aided finely graded Capacitive insulation for optimum electrical field distribution
  • Partial discharge free and low dissipation factor attributable to stable long-term performance
  • Shatter-proof oil end insulator
  • High seismic and SC load withstand capacity
  • Available with porcelain or composite insulator housing on air-side
  • Excellent thermal performance
  • Large size oil indicator for better visibility from distance and angles
  • Viton material O-rings for oil sealing
  • Special terminals available upon request
  • Potential for customization of BCT, oil end length, mounting flange to a large extent
  • Exact interchangeability with global reputed makes
  • Shortest lead times industry-wide
  • VCL/VCD/VCS Bushings are High voltage capacitance graded oil-impregnated paper insulated bushings
  • The Bushings comply with IEC 60137 standard s performance requirements for application in power transformers
  • The main component of Bushing is the Active part and is manufactured using insulating kraft paper wound around a central tube or solid conductor
  • During paper winding, aluminium foils are embedded in paper co-axially at pre-calculated locations to optimise the radial and axial electrical field along the bushing
  • After winding, the paper core is dried under vacuum at elevated temperatures and subsequently impregnated with high-quality vacuum dried and degassed Insulating mineral oil
  • The bushing is assembled in a controlled environment and filled under vacuum with vacuum dried and degassed Insulating Mineral oil
  • After oil filling, each Bushing is subjected to oil-filled over-pressure test for verification of joint sealing
  • All bushings are routine tested and type tested in accordance with IEC 60137

Our experienced team of design engineers offer a wide range of built to specification Air to Air Wall bushings and Oil to Oil OIP Bushings solutions wherein they work closely with the end-users / equipment designers from the project engineering stage to understand requirements of mounting, ambient environments, wall dimensions, through hole dimensions, cantilever and pollution requirements amongst many other things to arrive at the optimised wall through bushings design adapted for their end-use.